The LMCP series panel provides simple network capable lighting control enabling the automation of lighting functions throughout an entire facility. The HDR relays in the panel can respond directly to inputs from Digital Lighting Management (DLM) switches, occupancy sensors, daylight sensors, and input modules.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Runs scheduled and photocell events autonomously
- Easy setup via LMCT-100 handheld configuration tool
- HDR relays include switch for manual override even when panel is powered off
- Native BACnet communications for network control solutions
- Compatible with Digital Lighting Management switches, sensors and input devices
- 99 control groups accessible via handheld configuration tool
- UL 20 listed for receptacle circuit control
- Compatible with DLM occupancy sensors,single pole heavy duty relays
Specifications
General Info
Product Line | Wattstopper | ||
Color | Nickel | ||
UPC Number | 754182934508 | ||
Country Of Origin | United States | ||
Application Sector | Commercial |
Additional Information
Product Has Potential to Contribute to LEED | Yes | This product contributes to earning credits in the LEED rating system. Visit our LEED with Legrand webpage for more information. | |
DesignLights Consortium Qualified System | Yes | ||
Security | Yes | This product is ioXt certified | |
Product Environmental Profile | Yes |
Resources
Installation Instructions
DLM - LMCP-Accessory Mounting Plate Installation Instructions
pdf
DLM Control Panel with Emergency Relay Option Installation Instructions
pdf
DLM Relay Panel Interiors User Manual
pdf
DLM Relay Panel Interiors with 0-10V Dimming or Switched On/Off Installation Instructions (TriLingual)
pdf
View More
Product Environmental Profile
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
Can dimmers be used with this unit
This specific panel does not have dimming capability on its own, but the LMCP 0-10V PANEL will allow for 0-10v dimming without additional controls. The LMDM switch is recommended to go with the panel but there are other options available in the DLM family. Please contact your local Wattstopper Rep for more information.
Date published: 2024-02-26
If a Zone Control shows (12) fixtures on the Zone but (3) of them are on an Emergency circuit from an EM panel, would that mean (9) on normal power need to be wired to one control relay and (3) on Emergency on a 2nd control relay?
You do not need a relay per fixture, you need a relay per circuit per zone.
1 zone with1 normal circuit and 1 EM circuit would only need 1 HDR and 1 EM relay; or one relay and an ELCU.
Date published: 2024-02-12
Can I group 48 loads into 1 group button ?
Yes, you can group 48 loads into one group.
Date published: 2022-04-13
Does this system have an app for remote operation ?
The LMCP-48 does not have an app for its controls. You can however access the programming with a LMCT-100-2 handheld remote or with LMCS-100 software installed on a laptop (using an LMCI-100 dongle for the connection). Please contact Wattstopper Technical Support @ 800-879-8585 if you need further assistance.