Converter - 0-10V to ELV - 120 V(450W)/277V(1000W)
LDCM-PL-120-277-010V
Wattstopper
Bazaarvoice SAP Hybris Integration Version 2.8.1
The LDCM-PL-120-277-010V takes a 0-10V dimming signal and a fixed line voltage input and converts it to a reverse phase dimmed output for up to 1000W for a 277V load and 450W for a 120V load. One LDCM-PL can be used per run up to the maximum wattage. The LDCM-PL can be used per run up to the maximum wattage. The LDCM-PL is rated to directly mount to a junction box in a plenum space for easier installations and to meet building requirements.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Specifications
General Info
Product Line | Wattstopper | ||
Color | Gray | ||
UPC Number | 754182948840 | ||
Country Of Origin | China | ||
Product Series | LDCM | ||
Installation Location | Ceiling | ||
Application Sector | Commercial | ||
Standard | UL 8750, CSA C22 No. 250.13, ETL, cETL, RoHS | ||
Warranty Type | 5-Year | ||
Type | Converter |
Dimensions
Product Width US | 7.0 in | ||
Product Weight US | 0.91 lb | ||
Product Volume US | 46.5 cu in | ||
Product Depth US | 1.96 in | ||
Product Height US | 3.39 in |
Technical Information
Operating Temperature Min | -4 °F | ||
Dimming Compatibility | 0-10 V, Reverse Phase | ||
Maximum Power | 1000 W @ 277 VAC, 450 W @ 110-120 VAC | ||
Operating Temperature Max | 104 °F | ||
Input Voltage | 120/277 VAC | ||
Line Frequency | 60 Hz | ||
Mounting Type | 1/2 in Knockout | ||
Current Draw | 3.8 A | ||
Operating Temperature | -20°-40°C, -4°-104°F |
Resources
Cutsheet
Installation Instructions
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
On the load side of this device do you need a separate neutral for lights or does the dimming just dim on the load hot?
Thank you for your question. A separate output neutral is necessary and cannot be shared.
Date published: 2024-09-04
Does this device require a switched hot? Will the ELV output turn off or go to a low end 1% / 5% / 10% when 0-10V dimming voltage falls to 1V or below?
The LDCM-PL requires 110-120 or 277 constant voltage. The performance will depend on the fixture. The LDCM provides dimming only, it does not switch. We would use it in conjunction with a room controller which would switch the load to off when the load is 0% in the DLM system.
Date published: 2024-07-11
Bazaarvoice SAP Hybris Integration Version 2.8.1