Power Pack, 120-277V, 50/60Hz, 24VDC, 225mA, RJ45 Connector
BZ-50RC
Wattstopper
Bazaarvoice SAP Hybris Integration Version 2.8.1
The BZ-50 Universal Voltage Power Pack provides 24 VDC operating voltage to Wattstopper’s low-voltage occupancy sensors. This device is constructed with environmentally friendly materials and is RoHS-compliant.
Connection Type
RJ45
- RJ45
- Wire Leads
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Self-contained power supply relay system
- Efficient switching power supply providing optimized current output based on number of sensors
- LED indicates status of relay or if there is a low-voltage overcurrent
- The product meets the materials restrictions of RoHS
- Zero crossing circuitry for reliability and increased product life
- UL 2043 plenum rated for cost-effective installation
- 1/2”” snap-in nipple attaches to standard electrical enclosures through 1/2”” knockouts
Specifications
General Info
Product Line | Wattstopper | ||
UPC Number | 754182923496 | ||
Country Of Origin | China | ||
Application Sector | Commercial | ||
Warranty Type | 5-Year |
Dimensions
Product Width US | 2.8 in | ||
Product Weight US | 0.3 lb | ||
Product Volume US | 28.1 cu in | ||
Product Depth US | 1.7 in | ||
Product Height US | 2.2 in |
Additional Information
RoHS Compliant | Yes | This product meets the material restrictions of Article 4 of the RoHS Directive (2011/65/EU), including Commission Delegated Directive 2015/863. | |
Security | Yes | This product is ioXt certified |
Technical Information
Amperage | 20 A | ||
Connection Type | Wired |
Resources
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
I wired everything the way it says in the diagram but my motion sensor isn’t turning my lights off when I leave for 20min and the power back BZ-50 class 2 is flashing every 5 seconds seeing what the issue could be thanks.
Please contact Wattstopper Technical Support @ 800-879-8585 for troubleshooting assistance.
Date published: 2024-04-18
Can you use the Red 24VDC from 1 BZ-50 and connect to the blue input on another BZ-50 to control a load
Hi Luke,
No, you cannot hook up as described.
Please follow the wiring diagram below to control more than one BZ-50 power pack from a single sensor.
Date published: 2024-05-10
What is the Source/Sink limit in mA of the Blue Control Output wire?
The transformer in the BZ-50 provides up to 225 mA of 24VDC power for the low voltage devices. The relay in the BZ-50 is switching and therefore does not have a Source/Sink mA limit. The relay will output either 120v or 277v depending on your input voltage.
Date published: 2024-01-30
Trying to put these in an existing building, can I switch the power pack on and off with a switch in the room? Instead of the switch leg coming off the BZ-50?
Hello,
The BZ-50 will allow a standard Line voltage switch to be installed on the Red switch leg wire.
Date published: 2024-01-25
Can I use the BZ-50 to control 12watt Led wall lights? Max 3 fixtures, total 36w 120v
Yes, as long as you do not exceed the 20A load limit.
Date published: 2024-01-18
Is there a minimum load requirement for the BZ-50?
How much sensor can use this power pack
Date published: 2024-05-23
What is the recommended relay for the BZ-50?
Does the power pack needs a switch leg from the switch or can i use Switch leg from light for the sensor to work
Date published: 2022-10-31
What is the maximum wire length for the BZ-50 output using 18 AWG wire?
The following attached image is a Tech Bulletin regarding Voltage Loss. It discusses wires lengths, gauges, and the corresponding voltages losses.
Date published: 2022-05-31