Power Pack, 120-277V, 50/60Hz, 24VDC, 225mA,
BZ-200
Wattstopper
Bazaarvoice SAP Hybris Integration Version 2.8.1
The BZ-200 power pack switches connected loads On and Off in response to Wattstopper low voltage occupancy sensors. It also provides up to 225mA at 24VDC to power the sensors. This device is constructed with environmentally friendly materials and is RoHS-compliant.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Efficient switching power supply provides optimized current output based on number of sensors
- Includes short circuit and thermal protection
- LED indicates status of relay or presence of low-voltage overcurrent
- UL 2043 plenum rated for cost-effective installation
- UL listed for control of lighting and plug loads
- Tested to NEMA 410 criteria for electronic ballast and driver inrush current
- 1/2”” threaded nipple attaches to standard electrical enclosures through 1/2”” knockouts
Specifications
General Info
Product Line | Wattstopper | ||
UPC Number | 754182938032 | ||
Country Of Origin | China | ||
Application Sector | Commercial | ||
Warranty Type | 5-Year |
Dimensions
Product Width US | 3.0 in | ||
Product Weight US | 0.4 lb | ||
Product Volume US | 42.0 cu in | ||
Product Depth US | 1.4 in | ||
Product Height US | 3.0 in |
Additional Information
RoHS Compliant | Yes | This product meets the material restrictions of Article 4 of the RoHS Directive (2011/65/EU), including Commission Delegated Directive 2015/863. | |
Security | Yes | This product is ioXt certified |
Technical Information
Amperage | 20 A | ||
Connection Type | Wired |
Resources
Installation Instructions
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
Can I used it with Single Pole Momentary Switch, to controlle the load OFF?
The answer to your question would be yes it can be used with a single pole momentary switch.
Date published: 2023-07-17
Can the power pack turn the load off when the room is occupied? Load off when occupied
More information is needed to properly address your request. Please contact Wattstopper Technical Support @ 800-879-8585 for further assistance.
Date published: 2022-04-13
Can A BZ-200 be used with a dimmer switch?
Yes, a BZ-200 can be used with a DCLV2 dimming switch.
Date published: 2022-04-13
Can a BZ-200 be used for receptacle control?
Yes the BZ-200 can be used for receptacle control.
The Cutsheet for the BZ-200 specifically discusses it's use for plug load control.