The BZ-150 Universal Voltage Power Pack can provide 24 VDC operating voltage to Wattstopper’s lowvoltage occupancy sensors. In addition, the BZ-150 enables manual-on, hold-on, hold-off and load shed applications when used with lighting control panels or building management systems. This device is constructed with environmentally friendly materials and is RoHS-compliant.
- Send
- Save as PDF
-
Added to Favorites Go to favoritesRemove from favorites?Something went wrong. Please try again later.
Features
- Self-contained power supply relay system
- Efficient switching power supply providing optimized current output based on number of sensors
- LED indicates status of relay or if there is a low-voltage overcurrent
- Hold-on and hold-off inputs integrate with BMS, lighting control panels & other building systems
- Integrates with low-voltage momentary switch to control any 24VDC occupancy sensor
- The product meets the materials restrictions of RoHS
- Provides auto-on or manual-on field-selectable operating mode
Specifications
General Info
Product Line | Wattstopper | ||
UPC Number | 754182922918 | ||
Country Of Origin | China | ||
Application Sector | Commercial | ||
Warranty Type | 5-Year |
Dimensions
Product Width US | 2.8 in | ||
Product Weight US | 0.3 lb | ||
Product Volume US | 28.1 cu in | ||
Product Depth US | 1.7 in | ||
Product Height US | 2.2 in |
Additional Information
RoHS Conformant | Yes | This product meets the material restrictions of Article 4 of the RoHS Directive (2011/65/EU), including Commission Delegated Directive 2015/863. | |
DesignLights Consortium Qualified System | Yes | ||
Security  | Yes | This product is ioXt certified |
Technical Information
Amperage | 20 A | ||
Voltage | 120/277 V | ||
Connection Type | Wired |
Resources
White Papers & Tech Bulletins
Cutsheet
Installation Instructions
CAD Drawings
57-007-8 - Typical Wiring for BZ-150 Power Pack
png
57-007-9 - Typical Wiring for BZ-150 Power Pack Bi-Level Control with MANUAL ON
png
60-961 - Power Pack Hold On with Relay
dwg
60-961 - Power Pack Hold On with Relay
pdf
60-961 - Power Pack Hold On with Relay
png
60-961 - Power Pack Hold On with Relay
dxf
Typical Wiring for BZ-150 Power Pack Bi-Level Control with MANUAL ON
dwg
View More
Reviews
Bazaarvoice SAP Hybris Integration Version 2.8.1
Questions & Answers
what replacement to use since this was discontinued?
Hello David,
The BZ-150 is a available item, it has not been discontinued. Please use our Where to buy option on our website to locate local Wattstopper Distributors in your area
Date published: 2024-06-25
How many HB300BL3 could you operate using only 1 of the BZ150 power pack.
Hello Tony,
The BZ series power packs can operate a total of up to 15 HB-300B-L3s in parallel.
Date published: 2024-05-08
Can I install 2 lvsw 101 on 1 bz150 with 3 ci300 sensors and how would I wire that ? Thanks
Hi Tom,
Yes, multiple switches can be wired in parallel also multiple sensors can be hooked up in parallel to a BZ power pack. Follow the wiring diagram included with the product and hook up additional switches and sensors devices in parallel from there.
Date published: 2024-02-15
Would this be an alternative or replacement for ILC TR277?
Hi Cory,
Yes, It would be a good alternative. Please refer to the installation guide for proper wiring instructions.
Date published: 2023-06-29
The BZ -150 and DT-300 were recently specified for plug / receptacle control on a project we are bidding. Can you confirm if this is rated for receptacle loads ? ( 20 amp max) .
Hi Al,
The BZ-150 power pack is rated for up to a 20-amp load rating.
Date published: 2023-03-14
Can you Dim LED fixtures using 0-10 volts with a BZ-150. BAS will be dimming fixtures at off hours at a certain percentage.
Hello,
Please feel free to give Technical Support a call to further discuss your configuration.
legrand Contact information:
Phone #: 844-957-3783 - Option 1, followed by option 2 for Technical Support.
Monday - Friday | 8:00am - 6:00pm Eastern Standard Time (excluding holidays)
Best Regards,
Technical Support
Date published: 2024-03-24
How many ceiling mounted occupancy sensors DT-300 will one power pack BZ-150 operate
You can have up to 4 DT300 ceiling sensors, per power pack.
Date published: 2024-01-26
Can 2 power packs control 1 sensor?
Yes, attached below is a wiring diagram showing one sensor and up to 3 power packs being used.