Questions & Answers
Can I put an l630r in the poke thru and is there a cover for the recepticle?
Asked by: df
Hi,
The 6" poke thru will not be able to accept that. See the below link for information on our poke thrus and which kinds of receptacles can fit.
https://legrand.my.site.com/knowledgebase/s/article/Poke-Thru-Devices-Straight-blade-and-locking-receptacle-options-for-Evolution-poke-thrus
Thanks,
Answered by: Wiremold Tech Support
Date published: 2024-10-11
Do you sell replacement KO blanks for the 3/4" and 1 1/4" holes in the top?
Asked by: Jesse Widdop
Jesse,
Part number 6FFKIT-BK would be the replacement screw plug kit for that cover.
Thanks,
Answered by: Wiremold Tech Support
Date published: 2024-08-20
Can the 6ATCFF be converted to the 6ATC2P?
Asked by: Mike
Hello,
CAUTION: to prevent electrical shock, shut off the power to the poke thru prior to performing any work.
Yes, the furniture feed cover can be replaced with the 6CT/6CTC series covers. However, remember to add all device plates and any necessary bottom feed plates that may be required.
Note: The 1BHA will have to be ordered if adding the 175CHA, 1125CHA, 1PTHA, or 1BLH bottom housing assemblies. Additionally, the 1BHA with one of the previously listed bottom housing assemblies must be added if installing the 68REC receptacles and 5BLH blank with tunnel from one side to the other as the 15FFHA included with the 6ATCFF does not allow for use of the tunnel.
Thank you,
Answered by: Wiremold Tech Support
Date published: 2023-01-04
For thr 6atcffbk
Asked by: Dan hall
Hello,
Please send us an email to technical.support@legrand.us or give us a call at 844-957-3783. Select option 2 for Wiremold and 2 for Technical Support. We are available to assist with Wiremold products including the 6ATCFF series poke-thru.
Thank you,
Answered by: Wiremold Tech Support
Date published: 2022-12-19
Can the 6ATCFF Poke thru accommodate a quad outlet 3/4" conduit, and for A/V, and voice data utilizing a 2" conduit knockout? Thanks
Asked by: Mike Kotowski
Hi Mike,
The 6ATCFF is solely a furniture feed poke thru. For outlets and data/AV I would suggest the 6ATC2P version which comes with (2) 20A duplex receptacles and can accept up to 2" conduit using the 152CHA adapter. Please note when receptacles are in the box the low voltage must also have jacks / a disconnect point. The low voltage cables cannot be ran though the box at all times as the cover will remain option, possibly affecting the UL and fire rating of the poke thru. If you need any additional information, or have questions about this requirement please feel free to reach out to us directly at 1-844-957-3783, option 2 for Wiremold, followed by option 2 again for tech support. You can also email us directly at technical.support@legrand.us.
Answered by: Wiremold Tech Support
Date published: 2024-07-11
Can a 6ATC2P be converted to a 6ATCFF?
Asked by: Anonymous
Hello -
Yes, the 6ATC2P can be converted to a 6ATCFF by changing the cover plate. The 6CFFTC cover comes with a divider that can be installed in place of the receptacle and communication mounting plates. Bottom feed device plates can also be changed as needed.
Thank you
Answered by: Wiremold Tech Support
Date published: 2022-01-14